The elevation must not be above 2000m
Surrounding medium temperature limit to + 40 ℃, the lower limit of 25 ℃;
Installation site of air relative humidity when the highest temperature is + 40 ℃ not more than 50%, at a lower temperature can have higher relative humidity, such as 20 ℃ at 90%.Due to temperature change occasionally produce condensation special measures should be taken
Installation site pollution level 2;
Installation category main circuit for Ⅲ;
Installation method: vertical installation;
No significant vibration and shock
Model | Pole | Rated operating voltage Ue | Frequency Hz | Rated current In A | Power/W |
HSM8-80GQ | 1P+N | AC230V | 50Hz | 20,32,40,50,63 | ≤1.5 |
3P+N | AC400V/230V | 40,50,63,80 |
(alternate)The set values for the overvoltage action Uvo:275V;
Overvoltage recovery value Uvor:≤253V;
(alternate)The set values for the undervoltage action Uvu:160V;
Undervoltage recovery value Uvur:≥195V;
Over under voltage action time:≤1s;
Automatic closing delay time :20s~60s;